LESSON 9.3 — Daylighting
A. Standard Map
| Topic | Governing Source | Exam Focus |
|---|---|---|
| Daylight Factor definition and formula | IS 3646; ch13-part02 Sec 1.1 | NAT — DF = SC + ERC + IRC; E_i = DF × E_o / 100 |
| SC, ERC, IRC — behaviour with room depth | ch13-part02 Sec 1.1 | MCQ — which component dominates at rear of room |
| Target DF by space type | IS 3646 Parts 1–3; NBC 2016 | MCQ — classroom ≥ 2%; office ≥ 2%; corridor ≥ 0.5% |
| IS 3646 recommended illuminance | IS 3646 | MCQ — office 300; classroom 300–500; hospital ward 300; corridor 100 lux |
| Window-to-floor area ratio | NBC 2016; ECBC guidance | MCQ — range and why DF relationship is non-linear |
| Daylight devices — light shelves, clerestories, sun pipes, atrium | ch13-part02 Sec 1.2 | MCQ/MSQ — system, depth reached, best application |
| Glare — disability vs discomfort | CIBSE; author gap-fill | MCQ — definition, effect, control strategy |
| Glare control — blinds, louvres, frit, light shelf | ch13-part02; industry practice | MCQ — external vs internal; shading vs diffusing |
| Lumen method (artificial supplement) | ch13-part02 Sec 1.3 | MCQ/NAT-awareness — N = (E × A)/(F × U × M) |
Exam Anchor: DF is a ratio (percentage) under an overcast sky — it does not change with varying sky brightness. Interior illuminance = DF × E_o / 100, where E_o = 8,000 lux for Indian design sky. Source: IS 3646; ch13-part02.
B. Mechanism in Words
-
Define the metric: Daylight levels change continuously. DF normalises interior illuminance against the simultaneous exterior sky illuminance, yielding a stable geometric ratio for a given room. The ratio holds approximately constant across varying sky brightness as long as the sky distribution type does not change.
-
Decompose DF into three sources: Light reaches any interior point via three distinct paths — directly from visible sky (SC), after reflection from external surfaces (ERC), and after bouncing off internal surfaces (IRC). Each component dominates at a different location in the room. SC is largest near the window; IRC increasingly dominates deep in the room where no sky is directly visible.
-
Check adequacy against IS 3646 targets: Once DF is calculated or measured, compare it to IS 3646 minimum values for the occupancy type. If the DF is below the minimum, the design must widen or raise windows, use high-reflectance interior finishes, introduce secondary daylighting devices (light shelf, clerestory), or supplement with artificial lighting.
-
Select the right daylighting device for depth: Side windows are effective to ~5 m; light shelves extend useful daylight to 5–7 m by bouncing light onto the ceiling; clerestories serve 5–8 m in single-storey halls; atria and sun pipes carry daylight to zones unreachable by perimeter windows.
-
Manage glare as a parallel requirement: Maximising DF at a point can create glare if uncontrolled direct sunlight or bright sky patches enter the line of sight. Glare control — external louvres, internal blinds, frit glass, deep reveals, light shelves — must be designed concurrently, not as an afterthought.
-
Distinguish DF from dynamic metrics: DF is an instantaneous, static ratio under an overcast sky. It does not represent the percentage of hours above a threshold illuminance (that is daylight autonomy, a climate-based metric). These are distinct — high DF does not guarantee high daylight autonomy in monsoon-heavy climates.
-
Supplement where DF is unavoidable low: Core zones, basement levels, and north-facing single-aspect spaces will have low DF regardless of design effort. Apply the lumen method to size artificial lighting for these zones, targeting the IS 3646 maintained illuminance level.
C. Core Concept Explanations
C1. Daylight Factor — Definition, Formula, and Design Sky
Daylight Factor (DF) expresses interior illuminance as a percentage of exterior simultaneous illuminance under a standard overcast (CIE) sky:
DF (%) = (E_i / E_o) × 100
- E_i = illuminance at the interior reference point (lux)
- E_o = simultaneous exterior horizontal illuminance from an unobstructed sky (lux)
Design sky for India: IS 3646 and Indian daylighting practice use E_o = 8,000 lux for an overcast sky condition. Some references use 10,000–15,000 lux for a clear sky — the question will always specify which value to use.
Inverse formula for illuminance from DF:
E_i = DF × E_o / 100
Example: DF = 2.5%, E_o = 8,000 lux → E_i = 2.5 × 8,000 / 100 = 200 lux
DF components — additive:
DF = SC + ERC + IRC
| Component | Full name | Physical origin | Dominates where |
|---|---|---|---|
| SC | Sky Component | Direct view of the sky through the aperture | Near windows (within ~3 m) |
| ERC | Externally Reflected Component | Reflection off ground, pavements, opposite building facades | Near windows; higher in urban dense settings with light facades |
| IRC | Internally Reflected Component | Multiple bounces off internal surfaces (ceiling, walls, floor) | Deep in room (beyond ~4–5 m from window) |
Design implications:
– Increasing ceiling and wall reflectance raises IRC — most cost-effective way to improve DF at the rear of a room.
– Raising the window head height increases SC reach deeper into the room (sky visible from further back).
– ERC is largely fixed by the external context and cannot be easily designed in.
Source: IS 3646 Parts 1–3; ch13-part02 Sec 1.1.
C2. Target DF by Space Type — NBC / IS Practice
IS 3646 specifies both minimum DF and recommended maintained illuminance. The two are related but independently specified — a space may meet the lux target under artificial light without meeting the DF requirement for daylighting adequacy.
| Space Type | Minimum DF (%) | Recommended illuminance (lux) | Activity basis |
|---|---|---|---|
| Drawing office, drafting room | 4–5 | 750 | Very fine visual task |
| Classroom — general | 2 | 300 | Reading, writing |
| Office — general | 2 | 300 | Desk work |
| Library — reading room | 3 | 500 | Sustained reading |
| Hospital ward — general | 2 | 300 | Patient care, general observation |
| Hospital — examination room | — | 500–1,000 | Clinical visual task |
| Corridor / circulation | 0.5–1 | 100 | Way-finding, transition |
| Staircase | 1 | 100–150 | Safety, way-finding |
| Residential living room | 1 | 150–200 | Relaxed activity |
Exam Anchor: IS 3646 classroom minimum DF = 2%; office minimum DF = 2%; corridor minimum DF = 0.5%. Drawing offices require the highest DF (4–5%) in the standard building typologies. Source: IS 3646 Parts 1–3.
C3. Window-to-Floor Area Ratio — Recommended Ranges
The Window-to-Floor Area Ratio (WFR) is the ratio of glazed opening area to floor area of the room. Unlike WWR (window-to-wall), WFR directly links aperture size to the volume of space it must illuminate.
NBC 2016 guidance:
– Habitable rooms (residential): minimum WFR = 1/10 (10%) of floor area for light and ventilation.
– Schools and institutional buildings: WFR ≥ 1/6 to 1/5 of floor area recommended.
– Deep commercial floor plates: WFR required on perimeter only; core zones must rely on artificial light or secondary daylight devices.
Why DF is non-linear with WFR:
Doubling window area does not double DF at all points in the room. The relationship is non-linear for three reasons:
1. SC diminishes with depth faster than linearly — the solid angle subtended by the sky shrinks rapidly with distance from the window.
2. Obstruction effects — as windows are enlarged, the frame-to-glass ratio, glazing transmittance, and external obstruction angle all interact non-linearly.
3. IRC contribution plateaus — once walls and ceiling are well-lit by daylight near the window, additional window area adds diminishing IRC increment deep in the room.
Practical consequence: A 20% WFR does not guarantee twice the DF of a 10% WFR at the rear of a 12 m deep room. The depth-to-height ratio of the room has more influence on rear-desk DF than window width alone. Room depth ≤ 2.5 × ceiling height is the rule of thumb for effective daylighting with side windows.
Source: NBC 2016 Part 3; ECBC 2017 guidance; ch13-part02 Sec 1.1.
C4. Daylight Devices — Light Shelves, Clerestories, Sun Pipes, Atrium Wells
| Device | Mechanism | Effective depth | Best suited for |
|---|---|---|---|
| Side window | Sky Component dominant; SC drops with depth | ~5 m from aperture | All perimeter zones in any building type |
| Light shelf | Horizontal reflector at window head height; bounces high-angle sky light onto ceiling, increasing IRC in the rear zone; shields lower window from direct sun, reducing glare | 5–7 m | Deep open-plan offices; reduces glare simultaneously |
| Clerestory | High-level window strip above an adjacent lower roof or internal partition; sky light enters at high angle, penetrating deeper before hitting the floor | 5–8 m | Single-storey factories, assembly halls, schools with flat roofs |
| Skylight | Top-lit aperture; delivers near-vertical sky radiation; high SC directly below, rapid drop away from opening | Directly below (2–3 m radius) | Galleries, atria, stairwells, museum display spaces |
| Sun pipe / light tube | Reflective-lined tube with domed collector at roof and diffuser at ceiling level; carries daylight down through floors | 1–3 storeys | Basements, internal bathrooms, service corridors |
| Atrium well | Central void open to sky; secondary daylighting of interior facades; effectiveness depends on width-to-height ratio (W:H) and wall reflectance | Full building depth if W:H ≥ 1:1 | Hotels, offices, shopping centres with deep floor plates |
| LCP panels | Laser-cut acrylic redirects oblique high-angle light toward ceiling; installed in windows or skylights | 3–5 m beyond device | Retrofit applications; overgrazed facades |
Light shelf — dual benefit clarification:
The external portion shades the lower window zone from direct sun (reduces glare). The internal portion reflects high-angle sky light onto the ceiling (extends IRC reach). Both effects operate simultaneously and are the primary reason light shelves are preferred over simple tinted glass for deep offices in tropical climates.
Atrium W:H ratio:
– W:H ≥ 1:1 (wide, shallow atrium): floors near the base still receive useful diffuse sky light.
– W:H < 0.3:1 (narrow, deep atrium): lower floors receive very little daylight; the atrium functions mainly as a circulation void.
– Light-coloured atrium walls (reflectance ≥ 0.5) multiply effective reach by increasing IRC contribution to lower floors.
Source: ch13-part02 Sec 1.2; CIBSE Daylighting and Window Design (LG10).
C5. Glare — Disability vs Discomfort; Control Strategies
Glare occurs when a source in the visual field is significantly brighter than the adaptation level of the eye, degrading visual performance or causing discomfort.
Two types:
| Type | Definition | Effect on occupant | Reversibility |
|---|---|---|---|
| Disability glare | Bright source directly in or near the line of sight causes veiling luminance that physically reduces visual contrast and acuity | Reduces ability to read or perform a visual task — measurable loss of performance even if not perceived as discomfort | Immediate — ceases when source is removed from line of sight |
| Discomfort glare | Bright source in peripheral vision causes annoyance, distraction, and eye fatigue without necessarily reducing measurable visual acuity | Long-term occupant dissatisfaction; causes screen reflections, squinting, headaches | Cumulative — manifests over time; difficult to correlate to a single moment |
Glare metrics (awareness):
– Daylight Glare Index (DGI): Used for daylighting; scale 16 (just perceptible) to 28 (intolerable).
– Unified Glare Rating (UGR): Used for artificial lighting; scale 10–30; maximum 19 for offices.
Glare sources in daylighted spaces:
– Unshielded bright sky visible from a seated position.
– Direct sunlight patches on desks.
– High-contrast transition between a bright window and dark adjacent wall.
– Computer screen reflections of bright windows.
Glare control strategies — ranked by preference:
| Strategy | Type | How it works | Tradeoff |
|---|---|---|---|
| External horizontal louvres / brise-soleil | Shading | Intercepts direct solar beam before reaching glass | Fixed shading may block diffuse daylight in overcast conditions |
| Light shelf | Redirecting + shading | Shields lower window from direct sun; redirects upper sky light | Reduces window area below shelf; must be positioned at correct height |
| Deep window reveal | Geometry | Increases cut-off angle; sky visible from limited positions only | Reduces SC; increases structural reveal depth |
| Frit glass | Diffusing | Ceramic dot or line pattern baked onto glass; diffuses bright sky patches; reduces transmittance | Reduces VLT by 20–50%; permanent; no user control |
| Internal venetian blinds (adjustable louvres) | Blocking + redirecting | Slats angled to redirect light toward ceiling; occupant-controlled | Requires user cooperation; often misused (closed all day) |
| Internal roller blinds | Blocking | Reduces VLT; cuts glare when deployed | Eliminates daylight view when closed; defeats daylighting intent |
| High window placement (sill ≥ 1.8 m) | Geometry | Sky visible only from ceiling zone, not seated line of sight | Reduces SC to work plane; increases IRC via ceiling bounce |
Source: ch13-part02 Sec 1.1; CIBSE LG10; ASHRAE 90.1 daylighting provisions.
C6. IS 3646 Illuminance Table — Recommended Maintained Levels
IS 3646 (Parts 1–3) — Code of Practice for Interior Illumination — specifies recommended maintained illuminance for building occupancies. These are the artificial + daylight combined levels that must be maintained at the working plane throughout the service life of the lighting installation.
| Space / Occupancy | Recommended illuminance (lux) | Source |
|---|---|---|
| Fine drafting / drawing office | 750 | IS 3646 Part 1 |
| Library — reading areas | 500 | IS 3646 Part 1 |
| Classroom — general | 300 (minimum); 500 recommended | IS 3646 Part 2 |
| General office / clerical | 300 | IS 3646 Part 1 |
| Conference / boardroom | 300–500 | IS 3646 Part 1 |
| Hospital ward — general | 300 | IS 3646 Part 3 |
| Hospital — examination / treatment | 500–1,000 | IS 3646 Part 3 |
| Operating theatre | 10,000–20,000 (task); 1,000 (general) | IS 3646 Part 3 |
| Residential — living room | 150–200 | IS 3646 Part 2 |
| Residential — bedroom | 100–150 | IS 3646 Part 2 |
| Corridor / circulation | 100 | IS 3646 Parts 1–3 |
| Staircase | 100–150 | IS 3646 |
| Storage / plant room | 100–200 | IS 3646 |
Key exam values to memorise:
| Space | Lux |
|---|---|
| Office | 300 |
| Classroom | 300 (min) — 500 (recommended) |
| Hospital ward | 300 |
| Corridor | 100 |
| Drawing office | 750 |
Exam Anchor: IS 3646 specifies maintained illuminance at the working plane — the average level after accounting for lamp depreciation and luminaire dirt accumulation (maintenance factor M = 0.7–0.8). New installation illuminance is higher than the maintained value. Source: IS 3646 Parts 1–3.
D. Worked Numericals and Parameter Tables
D1. Worked NAT — DF Calculation with IS 3646 Adequacy Check
Problem: An office room in Mumbai is 10 m deep, 6 m wide, 3 m floor-to-ceiling height, with a single window on one short wall (2.4 m wide × 1.8 m high, sill at 0.9 m above floor). At a workstation located 7 m from the window, the following components are measured: SC = 0.8%, ERC = 0.2%, IRC = 1.4%. Design sky illuminance = 8,000 lux.
(a) Calculate the Daylight Factor at the 7 m workstation.
(b) Calculate the interior illuminance at that point under design sky.
(c) Does this meet the IS 3646 minimum DF for a general office? If not, state one design change that would increase IRC.
(d) What maintained illuminance (lux) would need to be provided by supplementary artificial lighting if the actual maintained illuminance target is 300 lux?
Solution:
(a) DF calculation:
DF = SC + ERC + IRC = 0.8 + 0.2 + 1.4 = 2.4%
(b) Interior illuminance under design sky:
E_i = DF × E_o / 100 = 2.4 × 8,000 / 100 = 192 lux
(c) IS 3646 adequacy check:
IS 3646 minimum DF for general office = 2%
Calculated DF = 2.4% ≥ 2% → DF requirement is satisfied.
However, illuminance of 192 lux is below the IS 3646 recommended maintained illuminance of 300 lux for offices. The room meets the daylighting ratio requirement but not the absolute illuminance target under design sky.
Design change to increase IRC: Paint ceiling and upper walls in high-reflectance finish (reflectance ≥ 0.70). IRC is directly proportional to the mean surface reflectance of the room. Increasing reflectance from a typical 0.4–0.5 to 0.7–0.8 can increase IRC by 40–80% at deep workstations.
(d) Supplementary artificial lighting required:
Required illuminance: 300 lux
Daylight-provided illuminance: 192 lux
Supplementary artificial lighting needed: 300 − 192 = 108 lux
Answer summary: DF = 2.4% (meets minimum of 2%); E_i = 192 lux (below 300 lux target); 108 lux of supplementary artificial light needed; increase IRC by painting ceiling white or light grey (reflectance ≥ 0.70).
D2. DF Component Behaviour — Reference Table
| Position in room | SC | ERC | IRC | Dominant component |
|---|---|---|---|---|
| 0–1 m from window | Very high (15–25%) | Low | Low | SC |
| 2–3 m from window | High (5–10%) | Moderate | Low | SC |
| 4–5 m from window | Moderate (2–5%) | Low | Moderate | SC + IRC |
| 6–8 m from window | Low (0.5–2%) | Very low | Moderate–High | IRC |
| > 8 m from window (deep zone) | Near zero | Near zero | IRC governs | IRC |
Note: Values are indicative ranges for a standard side-window room; actual values depend on window size, room geometry, and surface reflectances.
E. Common Confusions
-
DF = percentage of time above threshold: DF is an instantaneous ratio under an overcast sky condition — it says nothing about the temporal distribution of daylight. “Daylight autonomy” (the percentage of occupied hours when daylight alone meets the illuminance target) is a separate dynamic metric requiring climate data and simulation.
-
Higher WWR always improves DF at all points: Enlarging windows raises SC near the window but the IRC contribution deep in the room is limited by surface reflectances, room depth, and ceiling height, not just window area. Doubling WWR rarely doubles rear-of-room DF.
-
Lux = lumens: Lux (lm/m²) is illuminance — flux per unit area at the receiving surface. Lumens (lm) is the total luminous flux emitted by a source. A 1,000 lm lamp spread over 10 m² gives 100 lux; the same lamp focused on 1 m² gives 1,000 lux. The quantities are different and not interchangeable.
-
Light shelf increases total visible light in the room: A light shelf does not increase total light — it redirects it. The lower window zone is shaded (SC reduced there), while high-angle sky light is bounced to the ceiling (IRC increased deep in the room). The net effect redistributes light; the total may be similar or slightly reduced.
-
Glare is always caused by high illuminance: High illuminance alone does not cause glare. Glare is caused by high luminance contrast — a bright source against a much darker surround. A 500 lux classroom lit uniformly with diffuse overhead lighting is glare-free; a 200 lux room with an unshaded bright window can produce severe discomfort glare.
-
Frit glass eliminates glare: Frit reduces peak luminance by diffusing the bright sky patch, but it does not eliminate glare — it softens and spreads it. For full glare control, angular cutoff (louvres, deep reveals) is more reliable than diffusion alone.
F. Exam Traps
| Trap | Incorrect Belief | Correct Principle |
|---|---|---|
| DF = % of time above illuminance target | DF measures how often daylight is adequate | DF = instantaneous ratio E_i/E_o under an overcast sky; temporal adequacy is daylight autonomy — a different metric requiring dynamic simulation |
| Lux = lumens | Both measure light quantity in the same way | Lux = illuminance (lm/m²) at the receiving plane; lumens = total flux emitted by a source; they are numerically equal only when 1 lm falls on exactly 1 m² |
| High WWR automatically prevents need for artificial lighting | More glass = more daylight everywhere | DF at deep zones is governed by IRC (surface reflectance, room depth/height ratio) not just window area; a bright facade with poor interior reflectance still has poor rear-of-room DF |
| High WWR with no glare control is always acceptable | More daylight = better comfort | Large unshielded glazing creates disability and discomfort glare, especially for computer users facing or adjacent to windows; WWR increase must always be paired with glare control |
| IRC is the largest DF component everywhere | The largest component is always IRC | SC is largest near windows; IRC dominates only in deep zones (beyond 5–6 m) and only when surface reflectances are high |
| Design sky = 10,000 lux for IS 3646 | The Indian design sky value is universally 10,000 lux | IS 3646 practice uses 8,000 lux for overcast sky; some references cite 10,000–15,000 for clear sky; always check which sky condition the question specifies |
| Light shelf increases total light in the room | Light shelves add light to the deep zone | Light shelves redirect light — shading the lower window zone while bouncing high-angle sky light to the ceiling; total flux into the room may not increase |
| Disability glare and discomfort glare have the same effect | Both types of glare are equivalent | Disability glare physically reduces visual acuity (measured drop in contrast detection); discomfort glare causes annoyance and fatigue without necessarily reducing acuity; both must be controlled but by different standards |
| Atrium depth does not matter for daylighting | A narrow, tall atrium provides equivalent daylight to a wide shallow one | Narrow, deep atria (W:H < 0.3) deliver minimal daylight to lower floors; W:H ≥ 1:1 with high-reflectance walls is required for effective atrium daylighting to the base |
| IS 3646 specifies illuminance for new installations | IS 3646 values are initial illuminance when installation is new | IS 3646 specifies maintained illuminance — the design target must be met at end of maintenance cycle after lamp depreciation and dirt accumulation |
G. Answer-Writing Cues
NAT — DF calculation: “Step 1: Sum the three components — DF = SC + ERC + IRC. Step 2: Convert to illuminance — E_i = DF × E_o / 100, using E_o = 8,000 lux for Indian design sky unless stated otherwise. Step 3: Compare to IS 3646 minimum DF for the space type and to the recommended maintained illuminance. State whether both are met.”
MCQ — which DF component dominates at depth: “At distances greater than 5–6 m from a side window, the Sky Component (SC) approaches zero because no sky is visible from that location. The Internally Reflected Component (IRC) then dominates — light has been bounced multiple times off ceiling, walls, and floor before reaching the deep zone. IRC can be increased by raising surface reflectances.”
MSQ — glare control methods: “Glare from windows can be controlled by: (a) external shading devices (louvres, brise-soleil) that intercept the solar beam before reaching glass — most effective; (b) light shelves that shade the lower window while redirecting high-angle light; (c) frit glass that diffuses peak luminance of the sky patch; (d) internal adjustable venetian blinds for occupant control. Roller blinds fully eliminate glare but also eliminate the daylight benefit.”
MCQ — DF vs daylight autonomy: “Daylight Factor is a static, geometry-based ratio measured under an overcast sky — it does not capture climate variability or time-of-day variation. Daylight autonomy (a climate-based metric) measures the fraction of annual occupied hours in which daylight alone provides the target illuminance, requiring hourly climate data and simulation. High DF does not guarantee high daylight autonomy in a predominantly overcast or monsoon climate.”
H. PYQ Linkage Note
| Topic | Exam appearance | Pattern |
|---|---|---|
| DF formula as NAT | GATE AR — SC + ERC + IRC given; calculate DF and illuminance | Standard 2-step NAT; most commonly uses E_o = 8,000 lux; answer in lux |
| Which component dominates at rear of room | MCQ — deep zone: SC, ERC, or IRC? | IRC dominates; SC near zero beyond 6–8 m |
| IS 3646 lux values | MCQ — match space type to illuminance target | Office 300; classroom 300/500; corridor 100; drawing office 750 |
| Disability vs discomfort glare distinction | MCQ — which type reduces visual acuity? | Disability glare; discomfort causes annoyance not performance loss |
| Light shelf function | MCQ — what does a light shelf do? | Dual function: shade lower window + redirect high-angle sky light to ceiling |
| DF vs daylight autonomy | MCQ — which metric requires climate simulation? | Daylight autonomy; DF is geometry-only, static |
| WFR for habitable rooms | MCQ — NBC minimum window area | 1/10 of floor area for light + ventilation |
I. Mini-Check — Lesson 9.3
Q1. (NAT) A library reading room is 12 m deep, 8 m wide, with clerestory windows on one long wall. At a reading table 9 m from the window wall, the components are: SC = 0.4%, ERC = 0.1%, IRC = 1.6%. Design sky illuminance = 8,000 lux. Calculate: (a) the Daylight Factor at the reading table, and (b) the interior illuminance under design sky.
Answer:
(a) DF = SC + ERC + IRC = 0.4 + 0.1 + 1.6 = 2.1%
(b) E_i = DF × E_o / 100 = 2.1 × 8,000 / 100 = 168 lux
IS 3646 recommends 500 lux for library reading areas. The daylight level of 168 lux is well below target — artificial supplementary lighting of at least 332 lux is required. The DF of 2.1% meets the general office minimum of 2%, but library reading is a more demanding task.
Q2. (MSQ) Which of the following statements about the Daylight Factor (DF) are correct? Select ALL that apply.
(A) DF is a ratio of interior to exterior illuminance expressed as a percentage under an overcast sky condition.
(B) A high DF guarantees that a room will achieve its target illuminance for the majority of occupied hours throughout the year.
(C) The Sky Component (SC) is typically the dominant contributor to DF at locations more than 8 m from a window.
(D) DF = SC + ERC + IRC, and all three components are additive.
(E) In India, the design overcast sky illuminance commonly used with IS 3646 is 8,000 lux.
Answer: (A), (D), (E)
(B) is wrong — high DF does not guarantee temporal adequacy; daylight autonomy requires dynamic climate simulation. (C) is wrong — beyond 6–8 m, SC approaches zero and IRC dominates, not SC.)
Q3. (MCQ) An architect installs a light shelf at window head height (2.4 m sill, 2.8 m head, light shelf at 2.2 m) in a deep open-plan office. What is the primary effect on daylighting distribution in the room?
(A) Total luminous flux entering the room increases because the shelf reflects additional external light inward.
(B) The lower window zone receives more direct sky light because the shelf blocks heat from the upper portion.
(C) High-angle sky light is redirected onto the ceiling, increasing IRC in the deep zone, while direct sun is shaded from the lower window, reducing glare near the window.
(D) The light shelf replaces the need for artificial lighting in the deep zone.
Answer: (C)
A light shelf redirects (does not add) light — the shelf reflects high-angle sky light from above onto the ceiling, boosting IRC in the rear of the room. Simultaneously it shades the lower window zone from direct sun, reducing glare. It does not increase total flux (A is wrong), it does not affect heat (B is wrong), and it cannot eliminate the need for artificial light in a 12 m deep room (D is wrong).
Q4. (MCQ) Which of the following correctly matches a space type with its IS 3646 recommended maintained illuminance?
(A) General office — 500 lux; hospital ward — 100 lux; corridor — 300 lux
(B) General office — 300 lux; hospital ward — 300 lux; corridor — 100 lux
(C) General office — 750 lux; hospital ward — 300 lux; corridor — 200 lux
(D) General office — 300 lux; hospital ward — 500 lux; corridor — 150 lux
Answer: (B)
IS 3646: general office = 300 lux; hospital ward (general) = 300 lux; corridor = 100 lux. Option (A) reverses ward and corridor values. Option (C) uses 750 lux which is the drawing office standard. Option (D) assigns 500 lux to hospital ward which is the examination room level, not the general ward.
Q5. (MCQ) A south-facing open-plan office in Chennai has a fully glazed curtain wall (WWR ≈ 70%) with no external shading. Occupants consistently pull down roller blinds during working hours despite sufficient daylight. What is the most likely primary reason?
(A) The office has insufficient lux levels — the glazing area is too small for adequate daylighting.
(B) Discomfort glare from unshielded bright sky and direct sunlight entering the line of sight of screen users makes the bright glazing intolerable despite high illuminance.
(C) The Daylight Factor is below the IS 3646 minimum of 2% for offices.
(D) The building does not comply with ECBC WWR limits, causing structural overheating.
Answer: (B)
Roller blinds are closed not because there is too little light (WWR 70% in Chennai provides abundant daylight) but because uncontrolled direct sun and bright sky patches produce severe discomfort and disability glare at screen workstations. High WWR without glare control defeats the daylighting intent — occupants blank out glazing entirely, adding artificial lighting load. The fix is external shading (louvres, brise-soleil) or a light shelf that shades the lower zone while admitting diffuse sky light.