LESSON 9.1 — Advanced Thermal Performance
A. Standard Map
| Topic | Governing Source | Exam Focus |
|---|---|---|
| U-value calculation | IS 3792:1978; ECBC 2017 | NAT — layered wall R-sum → U = 1/R_total |
| ECBC envelope compliance | ECBC 2017 (BEE) | MCQ — max U by climate zone; prescriptive vs WBP path |
| WWR limits | ECBC 2017 Table 4 | MCQ/MSQ — zone-specific limits; relationship with VLT |
| SHGC vs VLT | ECBC 2017; ASHRAE 90.1 | MCQ — solar heat vs visible light; spectrally selective glass |
| Thermal mass — lag/decrement | IS 3792; building physics | MCQ — effective climate zone; mass vs insulation role |
| PCM (Phase Change Material) | Author gap-fill; awareness | MSQ — benefit type; not a calculation item |
| Cool roofs — albedo + emissivity | ECBC 2017; ch13-part01 | MCQ — high reflectance + high emissivity; not white paint only |
| Green roofs | NBC 2016 awareness | MCQ — evapotranspiration cooling; insulation benefit |
| EUI (Energy Use Intensity) | ECBC / BEE | MCQ — kWh/m²/yr; envelope’s role in reducing EUI |
Exam Anchor: ECBC 2017 governs commercial buildings with connected load ≥ 100 kW or contract demand ≥ 120 kVA. Residential buildings are covered under ECoBC (Energy Conservation Code for Residential Buildings). Do not conflate. Source: ECBC 2017, BEE.
B. Mechanism in Words
-
Define the boundary: The building envelope is the thermal boundary between conditioned and unconditioned space — walls, roof, floor slab, and fenestration. Heat flows through this boundary in proportion to the area, the U-value of each element, and the inside-outside temperature difference (ΔT).
-
Calculate resistance layer by layer: Each opaque layer contributes R = d/k; the total wall resistance is R_total = R_si + ΣR_layers + R_so. Surface resistances (R_si = 0.13, R_so = 0.04 m²·K/W) are always added.
-
Convert to U-value: U = 1/R_total. This single number determines the rate of heat flow per unit area per degree of temperature difference. ECBC sets a ceiling on U — the lower the U, the better the insulation.
-
Verify against ECBC climate zone limits: Look up the correct zone (Composite, Hot-Dry, Warm-Humid, Temperate, Cold) and check whether the calculated U ≤ maximum permitted. If non-compliant, increase insulation thickness (solve for required R, then d = R × k).
-
Apply glazing metrics: On the fenestration portion, SHGC controls heat gain; VLT controls daylight. Low WWR buildings must use higher VLT glass to compensate for reduced glazing area. Spectrally selective coatings decouple the two — enabling high VLT with low SHGC simultaneously.
-
Leverage thermal mass for time-lag: High-density materials (brick, concrete) store daytime heat and release it at night — effective in hot-dry climates with large diurnal swings. PCMs exploit latent heat at a fixed temperature (typically 23–27°C for comfort range), offering equivalent thermal mass in far thinner construction.
-
Close the loop with roof strategy: A cool roof (high albedo reflectance ≥ 0.65 + high emissivity ε ≥ 0.90) minimises solar heat absorbed and maximises re-radiation. This directly reduces cooling load and EUI. Green roofs add evapotranspiration cooling and substrate insulation but require structural provisions for the additional dead load (typically 150–300 kg/m² for extensive type).
C. Core Concept Explanations
C1. ECBC 2017 Envelope — WWR Limits by Building Type and Climate
ECBC 2017, administered by the Bureau of Energy Efficiency (BEE), applies to new commercial buildings with a connected electrical load ≥ 100 kW or contract demand ≥ 120 kVA. Residential buildings fall under the separate ECoBC framework.
Compliance pathways:
| Path | Method | When used |
|---|---|---|
| Prescriptive | Each component independently meets max U-value, max SHGC, and other tabulated limits | Simple designs; no simulation required; conservative |
| Whole Building Performance (WBP) | Energy simulation model of proposed design vs a reference building built exactly to prescriptive limits; proposed must consume ≤ reference annual energy | Complex/irregular designs where one component trades against another |
Source: ECBC 2017, Section 4 (Envelope) and Section 12 (Compliance).
WWR (Window-to-Wall Ratio) limits: ECBC does not prescribe a single universal WWR limit; the code works through U-value and SHGC compliance. However, as glazing area increases relative to opaque wall area, the composite envelope U-value rises (glass has a higher U than insulated masonry). Industry practice and ECBC guidance recognise the following orientations as most solar-critical: west > east > south > north for Indian latitudes.
| Climate Zone | Practical WWR guidance | Reason |
|---|---|---|
| Hot-Dry (Jaipur, Jodhpur) | Keep WWR ≤ 30–40%; use north/south preference | High solar radiation; low humidity; mass more important |
| Warm-Humid (Mumbai, Kochi) | WWR ≤ 25–35%; shade all glazing | Diffuse sky + moisture load; ventilation critical |
| Composite (Delhi, Nagpur) | WWR ≤ 30–40%; shading + selective glass | Seasonal reversal; summer cooling dominates |
| Temperate (Pune, Bangalore) | WWR up to 50% feasible with selective glass | Mild temperatures; daylight benefit significant |
| Cold (Shimla, Leh) | Maximise south-facing glazing; limit north | Winter heating priority; high SHGC acceptable on south |
Source: ECBC 2017, Table 4; NBC 2016 Vol. 1 Part 8.
C2. U-value Standards by Climate Zone — Wall and Roof
ECBC 2017 specifies maximum U-values as a ceiling — the actual design must be at or below these values.
| Climate Zone | Max Wall U (W/m²·K) | Max Roof U (W/m²·K) | Roof rationale |
|---|---|---|---|
| Composite | 0.44 | 0.40 | High diurnal swing; roof gains large |
| Hot-Dry | 0.40 | 0.40 | Intense solar; greatest cooling load |
| Warm-Humid | 0.44 | 0.40 | High solar + humidity load |
| Temperate | 0.44 | 0.40 | Moderate climate; standard envelope |
| Cold | 0.35 | 0.30 | Heating load dominates; tightest limits |
Key insight: Roof U-value limits are equal to or tighter than wall limits in all zones because roofs receive the highest solar irradiance (horizontal surface, maximum exposure). In the Cold zone, the wall limit is the tightest of all zones (0.35) because winter heat loss through walls is the dominant energy concern.
Source: ECBC 2017, Tables 4.1 and 4.2; BEE Climate Zone Map.
C3. SHGC vs VLT — Why the Pairing Matters in Hot Climates
VLT (Visual Light Transmittance): The fraction of the visible portion of the solar spectrum (380–780 nm) transmitted through glazing. Clear glass ≈ 0.85–0.90; tinted glass ≈ 0.20–0.50.
SHGC (Solar Heat Gain Coefficient): The fraction of total incident solar energy (visible + near-infrared, ~300–2500 nm) that passes through the glazing system — both directly transmitted and secondarily re-radiated inward. Range: 0 to 1. Lower SHGC = less heat gain.
| Glazing type | VLT (approx.) | SHGC (approx.) | Suitability |
|---|---|---|---|
| Clear single-pane | 0.88 | 0.86 | Cold climates (south-facing passive solar) |
| Bronze/grey tinted | 0.40 | 0.55 | Partial solar control; sacrifices daylight |
| Reflective (metallic) | 0.20 | 0.25 | High solar rejection; poor daylight; glare to exterior |
| Spectrally selective Low-E | 0.65–0.72 | 0.25–0.35 | Optimal for hot Indian climates — high daylight + low heat |
The design tension: Reducing glazing area (WWR) cuts heat gain but also cuts daylight, pushing occupants to use artificial lighting. The energy-optimal solution in hot climates is: low WWR (≤40%) + spectrally selective glass with high VLT (≥0.50) + low SHGC (≤0.35) — admitting sufficient daylight through modest glazing while rejecting solar heat.
Exam Anchor: Low WWR does not automatically mean adequate daylighting — it only works if VLT is high enough to compensate for the reduced aperture. Source: ch13-part01; ECBC 2017 Section 4.4.
C4. Thermal Mass — Night Purging, Lag, Decrement, and PCM
Time lag (φ): The number of hours between peak outdoor temperature and peak indoor temperature. Thick dense walls increase lag. A 300 mm brick wall may have a lag of 8–10 hours, meaning peak internal temperature occurs after sunset — useful in hot-dry climates where outdoor temperatures cool significantly at night.
Decrement factor (f): The ratio of the amplitude of the indoor temperature swing to the amplitude of the outdoor temperature swing. A low decrement factor (e.g., 0.10–0.20 for thick masonry) means the indoor temperature barely oscillates even when the exterior swings wildly. Lightweight steel cladding has f ≈ 0.8–0.9 (poor dampening); 300 mm brick has f ≈ 0.10–0.20 (good dampening).
| Construction | Approx. Lag (hrs) | Approx. Decrement Factor |
|---|---|---|
| 12 mm metal cladding | < 1 | ~0.90 |
| 100 mm lightweight concrete | 2–3 | ~0.60 |
| 200 mm brick | 5–7 | ~0.30 |
| 300 mm brick / dense concrete | 8–12 | ~0.10–0.20 |
Night purging: After storing heat during the day, thick mass walls discharge stored heat to the cooler night air when windows are opened. This pre-cools the building for the following day. Effective only where diurnal range > ~10°C (hot-dry climates). In warm-humid climates with minimal day-night differential, this strategy yields no benefit.
PCM (Phase Change Materials): Materials that absorb or release latent heat at a near-constant temperature during the phase transition (e.g., solid ↔ liquid). Organic PCMs (e.g., paraffins) and inorganic eutectic salts are encapsulated in boards, plaster, or panels. A PCM board 15–20 mm thick can provide the thermal mass equivalent of 100–150 mm of concrete. Exam awareness: PCMs do not change U-value; they change the dynamic thermal response (lag and decrement). They are relevant in lightweight prefabricated construction where dead load constraints prevent use of heavy masonry.
Source: IS 3792:1978; building physics — Szokolay (2008); ECBC 2017 compliance guidance.
C5. Heat Island Mitigation — Cool Roofs, Green Roofs, Urban Albedo
Cool roofs: Require two simultaneous properties:
– High solar reflectance (albedo) ≥ 0.65: Minimises solar energy absorbed in the first place (Reflectance + Absorptance = 1).
– High thermal emittance (ε) ≥ 0.90: Maximises re-radiation of any absorbed heat as longwave infrared.
A white painted surface alone does not guarantee a cool roof — paint can degrade, and some white paints have lower emissivity than expected. Engineered products (white TPO membrane, cool-colour elastomeric coating, reflective metal panels) are specified for ECBC and green rating compliance.
| Surface | Solar Reflectance | Emissivity | Classification |
|---|---|---|---|
| Dark asphalt | ~0.05 | ~0.90 | Hot roof — absorbs, then radiates |
| Polished aluminium | ~0.85 | ~0.05 | Reflective but NOT a cool roof (low ε) |
| White painted concrete | ~0.70 | ~0.90 | Approaches cool roof |
| White TPO/PVC membrane | 0.65–0.85 | 0.85–0.92 | ECBC cool roof |
| Green roof (vegetated) | ~0.25–0.40 | High (vegetation) | UHI mitigation via evapotranspiration |
Green roofs: Substrate (growing medium) + vegetation + drainage layer. Reduce peak cooling load through: (a) evapotranspiration cooling, (b) substrate insulation effect, (c) reduced stormwater runoff. Extensive green roofs (substrate 50–150 mm, sedum/succulents) impose dead load of ~80–200 kg/m²; intensive green roofs (>200 mm substrate, shrubs/small trees) impose 300–600 kg/m² — require structural uprating.
Urban albedo strategy: Increasing the aggregate reflectance of urban surfaces (roofs + pavements) raises the urban albedo, reducing absorbed solar radiation city-wide and lowering ambient temperature by 1–3°C in highly-built areas.
Source: ECBC 2017 Section 4 (Cool Roof), ch13-part01; BEE cool roof guidance.
C6. EUI / Envelope Interaction — Concept-Level
Energy Use Intensity (EUI) = Total annual building energy consumption ÷ Gross conditioned floor area, expressed in kWh/m²/year (or kBtu/ft²/year in US practice). Lower EUI indicates a more energy-efficient building.
Envelope’s role in EUI:
– HVAC typically accounts for 40–60% of commercial building energy in India.
– Every 0.1 W/m²·K improvement in wall U-value reduces heating/cooling load proportionally to ΔT × area.
– Improving roof U-value has disproportionate impact relative to wall U-value because roofs have larger ΔT from solar exposure.
– Reducing WWR from 60% to 30% with spectrally selective glazing can reduce annual cooling energy by 15–25% in composite climate buildings (order-of-magnitude awareness; specific values depend on simulation).
ECBC star rating system (ECBC+, SuperECBC):
| Label | EUI reduction vs baseline | Status |
|---|---|---|
| ECBC | Meets ECBC 2017 minimum | Mandatory (notified states) |
| ECBC+ | ~25–35% better than ECBC | Voluntary |
| SuperECBC | ~50% better than ECBC | Voluntary |
Source: BEE ECBC 2017 User Guide; ECBC+ and SuperECBC labels, BEE.
D. Worked Numericals and Parameter Tables
D1. Worked NAT — Layered Wall U-value Calculation and ECBC Compliance Check
Problem: A commercial office building is located in Nagpur (Composite zone). The proposed exterior wall section is: 12 mm cement plaster external (k = 0.72 W/m·K) → 230 mm burnt clay brick (k = 0.80 W/m·K) → 40 mm expanded polystyrene (EPS) insulation (k = 0.035 W/m·K) → 12 mm gypsum plaster internal (k = 0.40 W/m·K). Surface resistances: R_so = 0.04 m²·K/W; R_si = 0.13 m²·K/W. Calculate U-value. Does it comply with ECBC 2017 for the Composite zone?
Solution:
| Layer | d (m) | k (W/m·K) | R = d/k (m²·K/W) |
|---|---|---|---|
| External surface (R_so) | — | — | 0.040 |
| External cement plaster | 0.012 | 0.72 | 0.017 |
| Burnt clay brick | 0.230 | 0.80 | 0.288 |
| EPS insulation | 0.040 | 0.035 | 1.143 |
| Gypsum plaster (internal) | 0.012 | 0.40 | 0.030 |
| Internal surface (R_si) | — | — | 0.130 |
R_total = 0.040 + 0.017 + 0.288 + 1.143 + 0.030 + 0.130 = 1.648 m²·K/W
U = 1 / 1.648 = 0.607 W/m²·K
ECBC 2017 maximum wall U for Composite zone = 0.44 W/m²·K
0.607 > 0.44 → Wall does NOT comply.
Remediation — find minimum EPS thickness for compliance:
Required R_total = 1 / 0.44 = 2.273 m²·K/W
Existing non-insulation R = 0.040 + 0.017 + 0.288 + 0.030 + 0.130 = 0.505 m²·K/W
Required insulation R = 2.273 − 0.505 = 1.768 m²·K/W
Required EPS thickness = R × k = 1.768 × 0.035 = 0.0619 m ≈ 62 mm
Answer: Proposed U = 0.61 W/m²·K (non-compliant). Minimum 62 mm EPS insulation required to achieve U ≤ 0.44 W/m²·K in the Composite zone.
D2. Worked NAT — Modified Wall: Add Air Gap
Problem (extension): The architect adds a 25 mm unventilated air gap between the EPS and gypsum plaster. R of unventilated air gap = 0.18 m²·K/W. Does the revised 40 mm EPS wall now comply?
Revised R_total = 1.648 + 0.18 = 1.828 m²·K/W
Revised U = 1 / 1.828 = 0.547 W/m²·K
0.547 > 0.44 → Still non-compliant. The air gap alone cannot substitute for adequate insulation thickness.
Answer: U = 0.55 W/m²·K; still fails Composite zone limit. Insulation must be increased to at least 62 mm EPS.
D3. ECBC Compliance Summary Table — Wall and Roof by Zone
| Climate Zone | City examples | Max Wall U (W/m²·K) | Max Roof U (W/m²·K) | Max SHGC (typical) |
|---|---|---|---|---|
| Composite | Delhi, Nagpur, Lucknow | 0.44 | 0.40 | 0.25 |
| Hot-Dry | Jaipur, Jodhpur, Ahmedabad | 0.40 | 0.40 | 0.25 |
| Warm-Humid | Mumbai, Kochi, Chennai | 0.44 | 0.40 | 0.25 |
| Temperate | Bangalore, Pune, Hyderabad | 0.44 | 0.40 | 0.40 |
| Cold | Shimla, Leh, Srinagar | 0.35 | 0.30 | 0.51 (south-facing) |
Source: ECBC 2017 Tables 4.1–4.3, BEE.
E. Common Confusions
-
k-value vs U-value confusion: k (W/m·K) is a material intrinsic property; U (W/m²·K) is a system-level property for a complete wall/roof assembly. Specifying a brick’s k-value does not give you a wall U-value without summing all layers and surface resistances.
-
Thermal mass vs insulation conflated: Insulation (low k) resists heat flow rate; thermal mass (high ρ × Cp) delays and dampens heat flow amplitude. Both serve different roles — a wall can have high mass but poor insulation (bare 400 mm concrete: high lag but U still ~1.5 W/m²·K without insulation).
-
Cool roof = white paint: White paint applied to an existing dark membrane improves reflectance but may degrade within 2–3 years. Cool roof requires engineered products with certified reflectance ≥ 0.65 AND emissivity ≥ 0.90 maintained over time.
-
Low SHGC = good in all climates: Low SHGC reduces cooling loads in hot climates; in the Cold zone (Leh, Shimla), high SHGC on south-facing glazing is desirable for passive solar heating. Zone-specific application is critical.
-
ECBC applies to residential buildings: ECBC 2017 applies only to commercial buildings meeting the connected load threshold. Residential buildings are governed by ECoBC (Energy Conservation Code for Residential Buildings), a separate and more recently notified code.
-
WBP path = relaxed code: The Whole Building Performance path is not a way to avoid compliance — the proposed building must still consume ≤ a reference building built exactly to prescriptive ECBC. WBP allows design flexibility, not reduced performance.
F. Exam Traps
| Trap | Incorrect Belief | Correct Principle |
|---|---|---|
| U = k | U-value of wall equals k-value of the dominant material | U = 1/R_total; includes all layers + surface resistances; never equals k |
| R-value additive only for same material | Total R is summed across all different layers | R_total = R_so + ΣR_i + R_si; different materials, same arithmetic |
| SHGC and VLT move together | Lower SHGC always means lower VLT | Spectrally selective coatings can give high VLT (≥0.60) with low SHGC (≤0.30) |
| Cool roof = any white or light-coloured surface | White paint alone qualifies as a cool roof | Cool roof requires certified solar reflectance ≥ 0.65 AND emissivity ≥ 0.90 — not paint colour alone |
| ECBC covers all buildings | ECBC 2017 is universal for all building types | ECBC 2017 = commercial (≥100 kW load); residential = ECoBC; do not conflate |
| Cold zone has highest U-value limit (least insulation needed) | Cold climates have loose envelope requirements | Cold zone has the tightest limits: wall U ≤ 0.35, roof U ≤ 0.30 — heating load drives stringency |
| Thermal mass works in all climates | Heavy walls always improve thermal performance | Thermal mass is effective in hot-dry climates (large diurnal swing for night purging); ineffective in warm-humid climates where no cool nights exist |
| PCM improves U-value | Adding PCM panels reduces steady-state heat flow | PCM affects dynamic thermal response (lag, decrement); it does not change U-value at all |
| Green roof is always ECBC-compliant as a cool roof | A vegetated roof with low albedo (~0.25) counts as cool roof | Green roofs reduce UHI via evapotranspiration but do NOT meet ECBC cool roof thresholds for reflectance unless verified |
| WBP path is less stringent than prescriptive | WBP path allows poorer envelope performance | WBP requires total energy ≤ prescriptive reference building; individual component flexibility, not overall performance relaxation |
G. Answer-Writing Cues
MCQ / thermal properties: “U-value is the reciprocal of total thermal resistance (R_total), which is the sum of all layer resistances (d/k) plus internal and external surface resistances. It is not a material property — it characterises the complete wall/roof assembly.”
NAT — compliance check: “Step 1: Calculate R for each layer (d/k). Step 2: Add R_so + all layer R values + R_si = R_total. Step 3: U = 1/R_total. Step 4: Compare against ECBC zone limit. Step 5: If non-compliant, set R_total = 1/U_max, solve for required insulation R, then d = R × k.”
MSQ — SHGC/VLT pairing: “In hot Indian climates, spectrally selective glazing achieves high VLT (≥0.60) with low SHGC (≤0.30), decoupling daylight from solar heat gain. Low WWR combined with high VLT glass minimises heat gain while maintaining adequate daylight — negating the need for artificial lighting despite reduced glazing area.”
MCQ — ECBC applicability: “ECBC 2017 applies to commercial buildings with connected load ≥ 100 kW or contract demand ≥ 120 kVA. Residential buildings fall under ECoBC. The prescriptive path requires individual component compliance; WBP path requires whole-building simulation showing energy consumption ≤ a reference building.”
H. PYQ Linkage Note
| Topic | Exam appearance | Pattern |
|---|---|---|
| U-value NAT | GATE AR — appeared as direct calculation; given k values and thicknesses; asked for U or required insulation thickness | Always include surface resistances (R_si, R_so); traps set by omitting them |
| ECBC climate zones | MCQ — which zone has tightest wall U limit? | Answer: Cold zone (0.35) — counter-intuitive to those who think hot climates need most insulation |
| SHGC vs VLT distinction | MCQ — which parameter controls solar heat gain vs daylight? | SHGC = heat; VLT = light; spectrally selective = high VLT + low SHGC |
| Cool roof properties | MCQ — which combination defines a cool roof? | High solar reflectance + high thermal emittance; both required |
| Thermal mass climate match | MCQ — in which climate is thermal mass most effective? | Hot-dry; large diurnal swing enables night purging |
| ECBC applicability | MCQ — residential vs commercial | ECBC = commercial only; ECoBC = residential |
| Prescriptive vs WBP | MCQ — which ECBC path requires energy simulation? | WBP (Whole Building Performance) path |
I. Mini-Check — Lesson 9.1
Q1. (NAT) A wall section consists of the following layers outward to inward: external surface resistance R_so = 0.04 m²·K/W; 15 mm cement plaster (k = 0.72 W/m·K); 200 mm autoclaved aerated concrete (AAC) block (k = 0.16 W/m·K); 12 mm internal plaster (k = 0.40 W/m·K); internal surface resistance R_si = 0.13 m²·K/W. Calculate the U-value of this wall in W/m²·K (round to two decimal places).
Answer:
– R_so = 0.040
– Plaster: 0.015/0.72 = 0.021
– AAC: 0.200/0.16 = 1.250
– Internal plaster: 0.012/0.40 = 0.030
– R_si = 0.130
– R_total = 0.040 + 0.021 + 1.250 + 0.030 + 0.130 = 1.471 m²·K/W
– U = 1/1.471 = 0.68 W/m²·K
Q2. (NAT) The wall in Q1 is to be used in a building in Leh (Cold zone). ECBC 2017 prescribes maximum wall U = 0.35 W/m²·K for the Cold zone. What is the minimum thickness (in mm) of additional EPS insulation (k = 0.035 W/m·K) that must be added to this wall to achieve compliance?
Answer:
– Required R_total = 1/0.35 = 2.857 m²·K/W
– Existing R_total = 1.471 m²·K/W
– Additional R required = 2.857 − 1.471 = 1.386 m²·K/W
– Required EPS thickness = 1.386 × 0.035 = 0.0485 m = 48.5 mm → round up to 49 mm
Q3. (MSQ) Which of the following correctly describe the Energy Conservation Building Code (ECBC) 2017? Select ALL that apply.
(A) ECBC 2017 applies to commercial buildings with a connected electrical load of 100 kW or more.
(B) The prescriptive path requires a whole-building energy simulation.
(C) In the Cold zone, the maximum wall U-value is the most stringent of all five climate zones.
(D) ECBC 2017 governs residential buildings in India.
(E) The Whole Building Performance path allows individual components to exceed prescriptive limits provided total building energy is ≤ the reference building.
Answer: (A), (C), (E)
(B) is wrong — prescriptive path requires no simulation; WBP does. (D) is wrong — residential buildings are governed by ECoBC, not ECBC 2017.)
Q4. (MCQ) A building in Chennai (Warm-Humid zone) uses tinted glass with VLT = 0.25 and SHGC = 0.30, and a WWR of 20%. Despite the low WWR, occupants consistently use artificial lighting during the day. What is the most likely cause?
(A) SHGC is too high, causing excessive glare.
(B) VLT is too low — insufficient visible light transmitted through the limited glazing area.
(C) The WWR exceeds ECBC limits for the Warm-Humid zone.
(D) SHGC and VLT are not independently controllable parameters.
Answer: (B)
Low WWR (20%) demands high VLT glass to compensate for the small aperture. VLT = 0.25 (deeply tinted) admits very little daylight through an already-small glazing area — forcing artificial lighting regardless of solar heat control.
Q5. (MCQ) Which of the following surface combinations correctly defines a “cool roof” as per ECBC 2017?
(A) Solar reflectance = 0.35; thermal emittance = 0.90
(B) Solar reflectance = 0.70; thermal emittance = 0.40
(C) Solar reflectance = 0.70; thermal emittance = 0.92
(D) Solar reflectance = 0.50; thermal emittance = 0.85
Answer: (C)
A cool roof requires BOTH solar reflectance ≥ 0.65 AND thermal emittance ≥ 0.90. Option (A) fails reflectance (0.35 < 0.65). Option (B) fails emittance (0.40 < 0.90). Option (D) fails reflectance (0.50 < 0.65). Only (C) meets both thresholds.